AS 176.3 Plug-in current transformer

Plug-in current transformers suitable for SlimLine XR size XR1 for primary nominal currents from 75 A to 250 A with a secondary nominal current of 5 A or 1 A (optionally 2 A), in accuracy classes 3, 1 and 0.5.

To install the converter within the specified strip, the use of a special busbar adapter – included in the ABB range of products – is required.

  • Therm. Nominal continuous current Icth: 1.0 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Rail 1: 17 x 6
  • Round conductor: 15.2 mm
  • Overall width: 45 mm
  • Height: 65 mm
  • Overall depth: 30 mm

Plug-in current transformers suitable for SlimLine XR size XR1 for primary nominal currents from 75 A to 250 A with a secondary nominal current of 5 A or 1 A (optionally 2 A), in accuracy classes 3, 1 and 0.5.

To install the converter within the specified strip, the use of a special busbar adapter - included in the ABB range of products - is required.

  • Therm. Nominal continuous current Icth: 1.0 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Rail 1: 17 x 6
  • Round conductor: 15.2 mm
  • Overall width: 45 mm
  • Height: 65 mm
  • Overall depth: 30 mm