KBR 44 Split core current transformers

Compact current transformer with divisible measuring core for primary nominal currents from 100 A to 600 A with a secondary nominal current of 1 A and 5 A.

Optionally available with 0 … 333 mV voltage output for use as a current sensor.

The 1 A variant of the KBR 44 is supplied with 2.5 m 2×0.75 mm² secondary cable. A 0.5 m 2×1.5 mm² cable is supplied for the 5 A variant.

  • Therm. Nominal continuous current Icth: 1.2 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Applied technical standards: DIN EN 61869-1 / 2, VDE 0414-9-1 / 2
  • Round conductor: 44 mm
  • Width: 72.2 mm
  • Height: 120.6 mm
  • Overall depth: 98 mm

Compact current transformer with divisible measuring core for primary nominal currents from 100 A to 600 A with a secondary nominal current of 1 A and 5 A.

Optionally available with 0 ... 333 mV voltage output for use as a current sensor.

The 1 A variant of the KBR 44 is supplied with 2.5 m 2x0.75 mm² secondary cable. A 0.5 m 2x1.5 mm² cable is supplied for the 5 A variant.

  • Therm. Nominal continuous current Icth: 1.2 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Applied technical standards: DIN EN 61869-1 / 2, VDE 0414-9-1 / 2
  • Round conductor: 44 mm
  • Width: 72.2 mm
  • Height: 120.6 mm
  • Overall depth: 98 mm