EAS 176.3 Plug-in current transformers – offsetting for tariff application

Plug-in current transformers suitable for SlimLine XR size XR1 for primary nominal currents from 150 A to 250 A with a secondary nominal current of 5 A or 1 A, in accuracy class 0.5, with type approval by PTB Braunschweig for use for accounting purposes.

To install the converter within the above-mentioned strip, it is necessary to use a special busbar adapter – included in the ABB range of products.

  • Therm. Nominal continuous current Icth: 1.2 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Rail 1: 17 x 6 mm
  • Round conductor: 15.2 mm
  • Width: 44 mm
  • Height: 65 mm
  • Overall depth: 30 mm
  • Declaration of conformity: in the download area

Plug-in current transformers suitable for SlimLine XR size XR1 for primary nominal currents from 150 A to 250 A with a secondary nominal current of 5 A or 1 A, in accuracy class 0.5, with type approval by PTB Braunschweig for use for accounting purposes.

To install the converter within the above-mentioned strip, it is necessary to use a special busbar adapter - included in the ABB range of products.

  • Therm. Nominal continuous current Icth: 1.2 x IN
  • Therm. Rated short-time current Ith: 60 x IN, 1 sec.
  • Max. Operating voltage Um: 0.72 kV
  • Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
  • Nominal frequency: 50 Hz
  • Insulation class: E
  • Rail 1: 17 x 6 mm
  • Round conductor: 15.2 mm
  • Width: 44 mm
  • Height: 65 mm
  • Overall depth: 30 mm
  • Declaration of conformity: in the download area