EAS 176.3
Plug-in current transformers – offsetting for tariff application
Plug-in current transformers suitable for SlimLine XR size XR1 for primary nominal currents from 150 A to 250 A with a secondary nominal current of 5 A or 1 A, in accuracy class 0.5, with type approval by PTB Braunschweig for use for accounting purposes.
To install the converter within the above-mentioned strip, it is necessary to use a special busbar adapter - included in the ABB range of products.
- Therm. Nominal continuous current Icth: 1.2 x IN
- Therm. Rated short-time current Ith: 60 x IN, 1 sec.
- Max. Operating voltage Um: 0.72 kV
- Insulation test voltage: 3 kV, Ueff, 50 Hz, 1 min.
- Nominal frequency: 50 Hz
- Insulation class: E
- Rail 1: 17 x 6 mm
- Round conductor: 15.2 mm
- Width: 44 mm
- Height: 65 mm
- Overall depth: 30 mm
- Declaration of conformity: in the download area