ECTB 51.35
Plug-in current transformers for tariff
Technical data:
- Therm. nominal continuous current Icth: 1.2 x IN
- Therm. nominal short-time current Ith: 60 x IN, 1 s
- Max. operating voltage Um: 1.2 kV, Urms
- Insulation test voltage: 6 kV, Urms., 50 Hz, 1 min
- Lightning impulse voltage: 12 kV, 1.2/50 μs
- Nominal frequency: 50/60 Hz
- Technical standards applied: DIN EN 61869, Part 1 + 2
- Harmonic measurements with load 0.2 VA – Sr pf1
- Measuring accuracy up to 20 kHz:
ε ≤ 2% | Δϕ ≤ 2°@ 0.05–10 kHz
ε ≤ 3% | Δϕ ≤ 3°@ 10–20 kHz
Dimensions:
- Bus bar 1: 50 x 12 mm
- Bus bar 2: 40 x 30 mm
- Circular conductor: 43.7 mm
- Installation width: 85 mm
- Installation height: 105.25 mm
- Overall installation depth: 52 mm