CTB 61.35 KS Small-signal current transformer

CTB – Small-signal current transformer with screwless connection technology “Cage Clamp®”, UL certified

CTB - Small-signal current transformer with screwless connection technology “Cage Clamp®”, UL certified

Dimensions:

  • Rail 1 in mm: 63x10
  • Rail 2 in mm: 50x30
  • Round conductor in mm: 43.7
  • Width in mm: 95
  • Height in mm: 114.86
  • Total installation depth in mm: 52

Technical data:

  • Rated continuous current Icth : 1.2 x Ipr
  • Rated short-time current Ith: 60 x Ipr , 1 sec., max 100 kA
  • Operating voltage Um: 1.2 kV
  • Insulation test voltage: 6 kV, Ue ff , 50 Hz, 1 min.
  • Nominal frequency: 50 Hz / 60 Hz
  • Insulation class : B

Downloads

Catalogue available shortly

Weitere Produkte

Other products